![]() ![]() If fault F114 persists, call Technical support. Replace control module if fault cannot be cleared. ![]() Reference Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives Installation Instructions Publication DRIVES-IN001. Reference 1321-Mxxx Common Mode Chokes Installation Instructions Publication 1321-IN001.Ĭheck for proper installation. PowerFlex 525 controller pdf manual download. Reduce motor generated noise by installing Rockwell-supplied common mode cores on the motor leads and lowering Parameter 440 to 2 kHz. View and Download Allen-Bradley PowerFlex 525 user manual online. Thanks so much in advance, August 24th, 2017, 04:19 PM. The manual says it could be the control board or grounding. Have any of you had this fault ever come up, and if so, what do you think would be the cause. We had a F 114 fault on the drive that shut the whole oven down. The recommendation is to connect C1/C2 to GND. We have a somewhat new PowerFlex 525 for an exhaust on a oven. Default is 20ms, can increase to 100msīolster the ground connection to minimize noise, which could have an impact on this issue. Increase RPI on the connection inside of RSLogix. Use managed switches with the drives to minimize the Ethernet communication traffic the drive is exposed to. Firmware flash files can be found at the Product Compatibility and Download Center. Ī fault F114 or F105 on a PowerFlex 523/525 drive can indicate that there is an excessive amount of common mode noise inside the cabinet. Actions that can be taken include:įirmware upgrade to version 2.002 or later may help mitigate this behavior. ![]() Here is a response from the knowledgebase.